DHD Trouble Shooting Guide

Click-on a symptom from the chart and you will be moved to information on suspect items or components and recommended solutions.

Problem causes & solutions are rated as "most likely cause" starting with number 1.

For example: under the Column - Low Air Flow, the Blower Rotation is indicated as the most likely cause.

 

High Dewpoint

Low Air Flow

High Air Flow

Over Temp

Under Temp

 Valves

 3

 6
 

 6
 

 Blower Rotation

 

 1
 

 1
 

 Process Blower Amps

 

 4

 1
   

 Regeneration Blower Amps

 8
       

Cooling Coil

 

 5
 

 5
 

 High Return Temperature

 4
       

 Regeneration Filter

 7
       

 Process Filter

 

 2

 3

 2
 

 Regeneration Air Flow

 6
   

 7
 

 Desiccant

 9

 9
     

 Air Leaks

 2

 7
   

 2

 Pressure at Hopper Air Outlet

 10
   

 9
 

 Vacuum at Hopper Air Inlet

       

 3

 Plugged Hopper

 

 8
 

 8
 

 Regeneration Heater Amps

 5
       

 Process Heater Amps

     

 3

 1

 Process Air Damper

 

 3

 2

 4
 

 Dewpoint Instrument

 1
       

Dewpoint Instrument | Back to Selection Chart

The Dewpoint Instrument uses air flow from the dryer to detect the dewpoint of the air leaving the drying system. A reading of -40 is typically considered optimum.

Over time the sensor in the dewpoint instrument may become contaminated or connections may loosen. Operation should be checked against another instrument to confirm actual dewpoint

If the instrument is faulty you should test to determine the cause: faulty mechanical connection, faulty or contaminated sensor, faulty cable or faulty dewpoint board. All of these tests are simple to perform.

To perform dewpoint instrument test:

1. Check sample cell for positive air flow. If no positive air flow check the lines going to the instrument.
2. Test sensor by placing in ambient and view readings - should climb to 0 degrees or higher.
3. Test cable by unplugging from sensor and view reading - should drop to -40 or lower.
4. Test dewpoint board by removing cable from board and view reading - should drop to -40 or lower.

Repair or replace components are required.


Air Leaks | Back to Selection Chart

Leaks must be detected and repaired or hose replaced as these leaks allow ambient (wet) air into the drying system, having a significant impact on drying. Some of the problems associated with air leaks are High Dewpoints, Low Air Flow through the drying system and Low Process Temperatures detected at the hopper. Some systems can be hard piped to eliminate the chance of flexible hose leakage.

Over time flexible dryer hose may develop pin hole air leaks. Also mechanical connections may loosen with vibration over time. Check mechanical fasteners. Tighten as required and then check hose for physical leaks. If leaks are detected the hose should be replaced.


Valves | Back to Selection Chart
Four-way valves channel the process and reactivation air flows to the appropriate desiccant beds. If the air flow is not directed to the appropriate bed the drying system can be adversely affected.

Some of the problems associated with misaligned valves are:

- High Dewpoints as moist regeneration air enters the process air system.
- Low Air Flow through the system as the process air fights against the regeneration air.
- High Process Temperatures at the hopper as regeneration air at 600 degrees F. is misdirected into the process air stream

Wiper blades should cover the duct ports inside the valve housing and position themselves on the valve seats at the end of the valve motor stroke. The two valves are controlled by the single valve actuator motor which simultaneously positions the wipers in positions parallel to one another.

To perform DHD valve leakage test.

1. Set dryer control to 32 degrees F.
2. Note position of valve. Approximate position of wiper blades on the shafts is indicated by notches in one end of each valve shaft.
3. Cycle the dryer to point where the Regeneration Blower is off. Check at the regeneration outlet for either positive air flow or vacuum. Either indicates leakage past the valve wipers.
4. If you still think leaking valves are causing system degradation proceed with the leakage test by blocking the Process Outlet and checking for leakage past the valve wipers at the regeneration outlet.
5. Use the controller to cycle the dryer to changeover and repeat the test.
6. Excessive leakage is considered to be present when 1 percent or more of rated CFM for the Process Blower passes the wipers.
7. If leakage is detected adjust linkage and wipers so that seating is complete on both sides of travel, or inspect wipers for damage.


High Return Temperature | Back to Selection Chart

When the temperature of the air returning from the hopper exceeds 150 degrees F. (66 C.) desiccant cannot adsorb as much moisture. This gives you higher dewpoints. The return air temperature must be lowered. Typically this is not a problem using UnaDyn's patented Pulse Cool Technology (PCT) but if you encounter a return air temperature problem the following may help.

Check the temperature of the air returning to the dryer from the hopper. If you cannot lower the process air temperature going into the hopper you must lower the temperature of the air returning from the hopper.

The use of a Return Air Cooler (Install in-line between the hopper and dryer on the return line) may be required to lower the return air temperature.

The flow of water through the coil may be either continuous or regulated by a temperature control valve. If you are using a cooling coil and suspect it is not cooling the air in the system you can determine if the water is adsorbing heat energy by noting the relative temperature of the inlet and outlet water lines.

The return air temperature to the dryer should be regulated to approximately 150 degrees F. 66 C.) or less for optimum performance.


Regeneration Heater | Back to Selection Chart

A faulty Regeneration Heater can cause incomplete desiccant regeneration and thus High Dewpoints. The heater amperage should be checked on each leg of the heater.

To perform heater test:

1. In control cabinet locate the regeneration heater contactor.
2. Use the controller to cycle to the dryer so that the heater is on.
3. Use an amp probe to check each wire coming from the contactor and record your findings.

If readings vary from leg to leg by more than 10 percent you may have a faulty regeneration element. Repair or replace as needed.


Process Heater Amps | Back to Selection Chart

A faulty Process Air Heater can cause Under Temperature if an element has failed in the open condition or Over Temperatures if an element has failed in the closed condition. Amperage should be checked on each leg to begin your diagnostics.

To perform heater test:

1. In control cabinet locate the regeneration heater contactor.
2. Set the process temperature to 32 degrees F.
3. Use an amp probe to check each wire coming from the contactor and record your findings.
If you detect amperage on any leg one of the elements has failed "closed" and over temperatures may result. Repair or replace as needed.
3. Raise the process temperature to a setting that is safe for your drying conditions but that will enable the heater to cycle on for testing.
4. Use an amp probe to check each wire coming from the contactor and record your findings.
If readings vary from leg to leg by more than 10 percent you may have a faulty regeneration element. Repair or replace as needed.


Regeneration Air Flow | Back to Selection Chart

The regeneration blower supplies air to the regeneration beds. Air must flow freely and correctly past the regeneration heater, past the valves and through the desiccant bed or the system will be adversely affected.

Problems associated with restricted, leaking or misdirected Regeneration Air Flow include:
High dewpoints develop as moisture laden air enters the process air stream. High Process Temperatures in the system as regeneration air at 600 degrees F. is misdirected into the process air stream.

Some of the causes of restricted air flow are:
Improper rotation of the blower wheel. Even if the wheel is rotating the wrong way it will deliver air to the system BUT not enough. Physically check rotation of the blower wheel.

A clogged blower wheel will severely restrict air flow. Check the blower wheel for build and clean or replace as needed. Clogged regeneration filter; this filter removes air borne particles from the return air stream entering the regeneration beds and should be checked and cleaned or replaced as required.

Misaligned wiper valves allow process air to enter the regeneration air flow. Valves should be adjusted as required. Leaks in the system allow air to escape which also degrades the system. They must be repaired as soon as possible


Regeneration Filter | Back to Selection Chart

A regeneration filter that is contaminated may restrict air flow and allow dirt to build up on the blower wheel. This causes incomplete desiccant regeneration and thus raising dewpoints.

To Check and Clean or Replace the Regeneration Filter:

1. Turn the dryer off.
2. Remove the scalloped knob holding the cover on over the filter.
3. Remove filter and check for contamination. Replace or Clean as needed.
4. Filter can be cleaned with solvent (if metal filter) then using compressed air from the inside out.
5. After complete drying (if solvent was used) return the filter to the housing. Replace cover and resume operation.


Regeneration Blower Amps | Back to Selection Chart

Air must flow freely past the regeneration filter, past the regeneration heater and through the desiccant bed. If it does not the desiccant cannot release its trapped moisture and high dewpoints develop.

The regeneration motor has been appropriately sized to produce enough velocity to move this moisture laden air to its exit through the regeneration air outlet. If the blower is not moving air at an appropriate rate you should test the blower for proper amperage draw. Look for appropriate nameplate readings at each leg of the heater.

To perform blower motor test:

1. In control cabinet locate the regeneration motor contactor.
2. Use the controller to cycle to the dryer so that the blower motor is on.
3. Use an amp probe to check each wire coming from the contactor and record your findings.
4. If readings vary from leg to leg by more than 10 percent you may have a faulty regeneration blower motor.
5. Faulty motors should be repaired or replaced immediately to avoid adverse affect to the drying systems.


Desiccant Maintenance and Testing | Back to Selection Chart

In DHD style dryers, air from the dehumidifier is heated by the process heater and circulated through the hopper of material, which gradually gives off some of its moisture to the surrounding air.

The moisture removed from the material is carried back to the dehumidifier, where it is adsorbed by the molecular sieve type desiccant and held there. If the desiccant is contaminated or degraded its ability to adsorb moisture is affected. Return air temperature must also be 150 degrees F or less for effective desiccant operation.

Some of the problems associated with faulty desiccant are:
High Dewpoints as moist air reenters the process air system.
Low Air Flow through the system as the process air fights against compacted, shifted or contaminated desiccant.

To check the Desiccant:
1. Remove the tower lid. The desiccant may have shifted during transit. It should sit level across the width of the tower. Simply level out the desiccant if it has shifted.
2. Perform a desiccant test if you feel the desiccant is faulty or has become contaminated.

a. Fill a 150 ml glass beaker with 45 ml (approximately 1.36 oz.) of water.
b. Measure water temperature and record. The water temperature should not be below 60 or above 85 degrees Fahrenheit.
c. Fill a 150 ml glass beaker with 45 ml (approximately 1.36 oz.) of regenerated type 4A molecular sieve (desiccant may be regenerated using the dryer or an oven - when using an oven.
d. Bake the desiccant at 400 degrees F. (220 degrees C.) for 2 hours, place in a sealed container and allow to cool to ambient temperatures before proceeding with the desiccant test.
e. Place a temperature probe in the beaker with the molecular sieve. Quickly pour the water into the beaker containing the molecular sieve, as you stir.
f. Never add the molecular sieve to water, since the resulting peak temperature can be as much as 10 degrees F. below what it should be.
g. Record the peak temperature which should be reached in 10-20 seconds.
h. Subtract the starting water temperature from the peak temperature of the mixture to get the resulting temperature rise.
i. A 40 degree F. temperature rise is considered an adequate reading and indicates that your desiccant is not contaminated.

If your desiccant is contaminated do not replace and begin operation without a thorough understanding of what could have contaminated the desiccant.

Volatiles may be passing the filter; a Plasticizer Coil may be needed. Simple housekeeping could be the problem; is the filter being check, changed or cleaned regularly. Make sure you know WHY the desiccant failed.


Process Blower Amps | Back to Selection Chart

Air must flow at the correct rate through the system. If it does not the system will experience High Air Flow or Low Air Flow depending on the problem with the blower. These seriously affect system performance.

Excess air flow may actually convey material from the hopper to the return air line. This clogs the line and degrades the system causing Under Temperature conditions at the hopper.

Low air flow does not allow the dry air from the dehumidifier to enter the hopper at enough velocity to remove moisture from the material effectively and may also contribute to Over Temperature at the hopper.

The process blower motor has been sized to produce enough velocity to move the air through the dehumidifying system. If the blower is not moving air at an appropriate rate you should test the blower for proper amperage draw.

To perform blower motor test:

1. Look for appropriate nameplate readings at each leg.
2. In control cabinet locate the process blower motor contactor.
3. Use an amp probe to check each wire coming from the contactor and record your findings.
4. If readings vary from leg to leg by more than 10 percent you may have a faulty regeneration blower motor.
5. Faulty motors should be repaired or replaced immediately to avoid adverse affect to the drying systems.


Blower Rotation | Back to Selection Chart

Air must flow at the correct rate through the system. If the blower is rotating in the wrong direction it cannot deliver the correct amount of air. This seriously affects dryer performance. If the wheel is turning in the wrong direction it will deliver air BUT not enough for correct operation and the rotation should be corrected immediately.

Two of the problems associated with incorrect blower rotation are Low Air Flow and Over Temperature conditions at the hopper.

To check the blower rotation remove the filter from the housing so you clearly see the blower wheel.

Open the control box and locate the blower motor contactor for the blower to be checked. Momentarily engage the contactor so the motor turns on.

Observe blower wheel rotation. It should rotate so that air is delivered to the desired components: Regeneration or Process. There is a directional arrow on the blower wheel housing that indicates the correct direction.


Cooling Coil | Back to Selection Chart

There are three cooling coils that can be used with these dryers: Plasticizer Cooler, Process Cooler and Return Air Cooler

The Plasticizer Cooler is used to condense volatiles from the return air stream before they enter the system and contaminate the desiccant and filters.

The Process Cooler is used when drying at temperatures below 120 degrees F. It lowers the temperature of the air leaving the dryer (which can typically reach 150 degrees F. because of residual heat from the desiccant beds) before it reaches the process heater and hopper.

The Return Cooler is used for drying at temperatures above 250 degrees F. It lowers the air temperature of the process air returning to the desiccant beds. If the return air temperature is not 150 degrees F. or lower the desiccant cannot adsorb moisture from the air stream.

A cooling coil that is clogged will cause Low Air Flow and Over Temperatures. Check the coil on a regular basis and clean as required.

If water is not delivered to the cooling coil at an appropriate rate it cannot do its job and High Dewpoints and Over Temperature can also result.

If you are using a cooling coil and suspect it is not cooling the air in the system you can determine if the water is adsorbing heat energy by noting the relative temperature of the inlet and outlet water lines.

The flow of water through the coil may be either continuous or regulated by a temperature control valve.


Process Filter | Back to Selection Chart

A process filter that is contaminated may restrict air flow enough to seriously degrade the drying system because of low air flow and the resulting Over Temperature conditions at the hopper.


An improperly positioned filter can allow dust and fines to contaminate the dryer and desiccant.

To Check and Clean or Replace the Process Filter:

1. Turn the dryer off.
2. Remove filter and check for contamination. Replace or Clean as needed.
3. Filter can be cleaned by using compressed air blowing from the inside out.
4. After completion return the filter to the housing. Replace cover and resume operation.


Process Air Damper | Back to Selection Chart

If the damper is not set appropriately the drying system cannot operate effectively.

Some of the problems associated with an incorrect damper setting are:
Low Air Flow; this restricts the system ability to remove moisture from the material. Low Air Flow also contributes to Over Temperature conditions at the hopper.

High Air Flow; this does not give the air enough time in the hopper to effectively remove the moisture and can also contribute to Under Temperature conditions at the hopper. Can also cause material "carryover", plugging filter, and return air lines.

Adjust the Process Air Damper so that the Process Blower draws name plate amperage.


Plugged Hopper | Back to Selection Chart

Over Temperatures result from the Low Air Flow caused if the hopper, spreader cone or return air line are plugged. Air cannot move through the system as it is designed to do.

Check the spreader cone and make sure it is properly seated in the hopper. If it is not, material may have bypassed the cone and entered the return air line. Clean the line, seat the spreader cone and begin operation.

If the spreader cone is properly seated check the spreader cone surface. If the cone is a perforated style the holes in the cone may have become clogged. After cleaning the cone return to normal operation.


Vacuum at Hopper Air Inlet | Back to Selection Chart

If you have Vacuum at the Hopper Air Inlet you can experience Under Temperature or Over Temperature conditions and High Dewpoint.

Vacuum at the hopper inlet can be caused by several things:

1. Valve Leakage caused by misaligned or worn valves. Check alignment and wear. Leakage here not only causes vacuum at the hopper inlet but over and under temperature conditions.
2. Desiccant Bed Leakage caused by bad gasketing or desiccant bed lids that are not seated to the tower or contaminated desiccant also cause vacuum at the hopper inlet. Check all systems and components for correct operation, fit and seal.
3. Improper adjustment of the process air damper.
4. The process air filter if allowed to become plugged will also cause vacuum at the hopper air inlet. Clean or replace the filter.
5. Hopper loaders can also contribute to vacuum at the air inlet. If the flapper is not sealing properly during loading air is being drawn from the hopper rather than from the material source. Check flappers for fit. Repair or replace as needed.


Positive Pressure at Hopper Air Outlet | Back to Selection Chart

If you have Positive Pressure at the Hopper Air Outlet you can experience Under Temperature conditions and High Dewpoint.

Positive Pressure at the hopper inlet can be caused by several things:
Misaligned or worn valves. Check alignment and wear. Leakage here not only can cause positive pressure at the hopper inlet but under temperature conditions.

The process air filter if allowed to become plugged will cause positive pressure at the hopper air outlet. Clean or replace the filter.

The regeneration air filter if allowed to become plugged will also cause positive pressure at the hopper air outlet. Clean or replace the filter.

A plugged or dirty Cooling Coil can also cause positive pressure. Inspect the coil and clean an necessary.

Improper adjustment of the process air damper.

Technical Support
telephone: 703-490-7009
fax: 703-490-7008
Email